Overview KFD0-TR-EX1 RTD Converter Features: 1-channel isolated barrier 24 V DC supply (loop powered) 2- or 3-wire Pt100 RTD input Output 4 mA ... 20 mA, temperature linearization selectable DIP switch selectable ranges Sensor breakage detection Functions This isolated barrier is used for intrinsic safety applications. It is a loop-powered isolator that converts the resistance from a 3-wire RTD in the hazardous area to a 4 mA ... 20mA signal in the safe area. A selectable analog linearization ensures a temperature linear 4 mA ... 20mA output between 25 °C ... 375 °C. It also features conveniently located DIP switches, rotary switches and potentiometers to make field calibration easy. FAQ Q: How about the warranty ? A: Swan provide 1 years warranty for all the goods from us. Q: Other supplier have a better price than yours? A: "To create more benefit for clients"is our belief, if you have a better price , please let we know , we will try best to meet your price and support you. Q: How to ensure product quality? A: Our technicians can provide you with more professional services and product testing. Q: Could you provide technology support to us? A: Yes, we have been in this field for many years, and we have very experienced and specialized technology staffs. Any question,welcome to contact us, we will try our best to help you. Recommended Products K-DUCT-BU-UPR-03 HID2096 S1SD-1DI-1R K-DUCT-BU-UPR-05 HIC2077 S1SD-1FI-1R K-DUCT-GY-UPR-03 HIC2081 S1SD-1AI-1U K-DUCT-GY-UPR-05 HID2061 S1SD-1AI-2C